Rockwell Automation GV3000/SE AC Drive Ver. 6.06 Hdwe Ref., Installation, and Troubleshooting Manual User Manual

Page 117

Advertising
background image

Compliance with Electromagnetic Compatibility Standards

C-9

C.4.1 Connecting the AC Mains Filter Output to the GV3000/SE Drive

Input

The following sections describe how to wire the AC Mains Filters to the GV3000/SE

drives.

C.4.1.1 Connecting AC Mains Filters M/N 2DF4283, 2DF4284, 2DF4285, and 2DF4286

The power leads that connect the output terminals of the AC Mains Filter to the drive’s

AC input terminals are included with the filter. The flexible conduit to be used with

these power leads is also provided. See figure C.5.

Place the flexible conduit’s hub in the drive’s wire entry hole that is in-line with the
filter’s output wiring opening. Route the leads through the conduit. Secure both ends

of the flexible conduit.

Trim the power leads to the proper length and connect them to the drive’s AC input
power terminals (R,S,T). Connect the green/yellow ground lead to the drive’s ground

terminal.

Note that the filter’s output leads are red, yellow, and blue. This color coding is

stenciled on the printed circuit board at the filter’s input power terminals to help

identify the filter’s output wiring relative to the filter’s input wiring.

When the drive is connected to three-phase AC input power, the three output leads
from the filter should be connected to the drive’s AC input power terminals as shown

in figure C.5.

Connect the filter ground wire (green/yellow) to the drive ground.

Continue with section C.4.2.

Figure C.5 – Typical Three-Phase Connections for AC Mains Filters

M/N 2DF4283, 2DF4284, 2DF4285, and 2DF4286

R/L1

S/L2

T/L3

GND

U/T1

V/T2

W/T3

GND

GV3000/SE

L

L

L

E(GND)

RED YELLOW BLUE YELLOW

AC Mains Filter

GREEN/

A

B

1

2

3

MOTOR

C

FILTER'S AC INPUT POWER

DRIVE'S AC INPUT POWER

Advertising