6-2
GV3000/SE AC Drive Hardware Reference, Version 6.06
Step 2. Connect the three-phase AC output power motor leads to the appropriate
output terminals.
On 1-60 HP drives, connect the motor leads to terminals U/T1, V/T2, W/T3
on the power terminal strip.
On 60-150 HP drives, connect the motor leads to terminals U, V, and W.
On 200-400 HP drives, connect the motor leads to terminals U/T1, V/T2, and
W/T3.
Step 3. Tighten the three-phase AC output power terminals to the proper torque
according to drive type as shown in table 5.2.
!
ATTENTION: Do not route signal and control wiring with power wiring in
the same conduit. This can cause interference with drive operation.
Failure to observe these precautions could result in damage to, or
destruction of, the equipment
ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if a
drive sharing a conduit is being serviced or installed, all drives using this
conduit should be disabled to eliminate the possible shock hazard from
cross-coupled motor leads. Failure to observe these precautions could
result in bodily injury.