About the Drive

2-15

2.8.1 Jumper Locations and Settings

Jumpers J4 and J17 on the Regulator board are factory-set for voltage in and voltage

out signals. Refer to figures 2.9, 2.10, and 2.11 for their locations on the Regulator

boards. If you need to change the jumpers’ settings, use the following procedures.

2.8.1.1 Setting the Analog Input Speed Reference Jumper (J4)

Jumper J4 is the analog speed/torque (U.000) reference jumper. This jumper selects

either +/- 10 VDC or 0-20 mA input. Parameters P.009, P.010, and P.011 are used in

conjunction with the jumper.

Note that if the position of jumper J4 is changed after the parameters are

programmed, the software will not recognize that the input reference or polarity has

been changed. Be sure to verify that parameters P.009, P.010, and P.011 are correct

before starting the drive. Refer to the GV3000/SE Software Start-Up and Reference

manual for more information.

Use the following procedure to set jumper J4:

Step 1. Turn off input power to the drive and wait five minutes.
Step 2. Remove the cover from the drive by unscrewing the four attaching screws.

On 200-400 HP drives, open the outer cabinet door.

Step 3. Verify that the DC bus voltage is zero by following the procedure in section

9.3.

Step 4. Locate jumper J4 on the Regulator board. Refer to figures 2.9, 2.10, and

2.11.

Step 5. Locate pin 1 on jumper J4. Move the jumper to the desired setting as shown

in figure 2.12.

Step 6. Reattach the cover. On 200-400 HP drives, close the outer cabinet door.
Step 7. Reapply input power.

!

ATTENTION: Do not alter the setting of any jumper not described in this

instruction manual. Failure to observe this precaution could result in

damage to, or destruction of, the equipment.

!

ATTENTION: DC bus capacitors retain hazardous voltages after input

power has been disconnected. After disconnecting input power, wait five

(5) minutes for the DC bus capacitors to discharge and then check the

voltage with a voltmeter to ensure the DC bus capacitors are discharged

before touching any internal components. Failure to observe this

precaution could result in severe bodily injury or loss of life.

!

ATTENTION: Do not operate 200-400 HP drives with the outer and inner

cabinet doors open due to possible exposure to high voltage. Close the

outer and inner cabinet doors before putting the drive into run. Failure to

observe this precaution could result in severe bodily injury or loss of life.