Wiring the Regulator Board Terminal Strip

7-17

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring the Output Status Relays

28

29

30

31

Normally-Closed Contact

(Form B)

Normally-Closed Contact

Common (Form B)

Normally-Open Contact

(Form A)

Normally-Open Contact

Common (Form A)

Both Form A and Form B contacts are rated for

250 VAC/30 VDC at 5 amps resistive or 2 amps inductive

load.

The following parameter must be set:

P.013: Output Relay Configuration

Note that depending on the setting of parameter P.013, the

relay coil will energize (the normally-open contact will close

and the normally-closed contact will open). Refer to the

GV3000/SE Software Start-Up and Reference manual for

more information.

28 29 30 31

User-Supplied

Parameter P.013 selects output indication.

N.C.
Com.

N.O.
Com

Device