Wiring the Regulator Board Terminal Strip
7-17
Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring the Output Status Relays
28
29
30
31
Normally-Closed Contact
(Form B)
Normally-Closed Contact
Common (Form B)
Normally-Open Contact
(Form A)
Normally-Open Contact
Common (Form A)
Both Form A and Form B contacts are rated for
250 VAC/30 VDC at 5 amps resistive or 2 amps inductive
load.
The following parameter must be set:
•
P.013: Output Relay Configuration
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close
and the normally-closed contact will open). Refer to the
GV3000/SE Software Start-Up and Reference manual for
more information.
28 29 30 31
User-Supplied
Parameter P.013 selects output indication.
N.C.
Com.
N.O.
Com
Device