3-8
GV3000/SE AC Drive Hardware Reference, Version 6.06
Standard reactors can be used on GV3000/SE drives with carrier frequency settings up to 8 kHz.
All reactors listed are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File #LR29753).
Table 3.10 – Recommended Motor Lead Lengths for Reliance Inverter Duty Motors
Maximum Lead Length in Feet with
460 VAC Motor
GV3000/SE
HP Rating
Filter Type
Carrier Frequency
2 kHz
4 kHz
8 kHz
1 to 2
None
500
500
500
3 to 5
500
500
500
7.5 to 10
750
500
500
15 to 20
800
500
500
25 to 60
800
500
500
75 to 100
800
500
500
125 to 150
800
500
500
200 to 400
1000
1000
1000
1 to 2
A 5% reactor/filter
at the drive.
1000
1000
1000
3 to 5
1000
1000
1000
7.5 to 10
1000
1000
1000
15 to 20
1000
1000
1000
25 to 60
1000
1000
1000
75 to 100
1000
1000
1000
125 to 150
1000
1000
1000
200 to 400
1000
1000
1000
Table 3.11 – Compatible Reactors
GV3000/SE
HP Rating
480 Volt
5% Reactor
GV3000/SE
HP Rating
480 Volt
5% Reactor
1
RL-00202
50
RL-08003
2
RL-00403
60
RL-08003
3
RL-00403
75
RL-10003
5
RL-00803
100
RL-13003
7.5
RL-01203
125
RL-16003
10
RL-01803
150
RL-20003
15
RL-02503
200
RL-25003
20
RL-03503
250
RL-32003
25
RL-03503
300
RL-40003
30
RL-04503
350
RL-50003
40
RL-05503
400
RL-50003