Rockwell Automation GV3000/SE AC Drive Ver. 6.06 Hdwe Ref., Installation, and Troubleshooting Manual User Manual

Page 31

Advertising
background image

About the Drive

2-17

Step 3. Verify that the DC bus voltage is zero by following the procedure in section

9.3.

Step 4. Locate jumper J17 on the Regulator board. Refer to figures 2.9, 2.10, and

2.11.

Step 5. Locate pin 1 on jumper J17. Move the jumper to the desired setting as shown

in figure 2.13.

Step 6. Reattach the cover. On 200-400 HP drives, close the outer cabinet door.
Step 7. Reapply input power.
Step 8. Verify that parameter P.012 is set correctly for either speed or current.

2.8.2 Wiring the Terminal Strip

The terminal strip on the Regulator board provides terminals for connecting customer

I/O devices. See figures 2.9, 2.10, 2.11, and 2.14. The following terminals are

provided:

Terminals 1-3: RS-232 connections

Terminals 4-9: encoder connections

Terminals 10-11: analog output connections

Terminals 12-15: analog speed/torque reference connections

Terminals 16-25: 24V DC digital input connections

Terminals 26-27: snubber resistor braking control connections
(1-10 HP Regulator boards only) for older Snubber Resistor Braking Kits

(for example, the M/N 2DB4010 series)

Terminals 28-31: status relay connections

Figure 2.13 – Jumper J17 Settings for Analog Outputs

J17

J17

10 VDC

Voltage Output Option

Pins 2-3

Current Output Option

Pins 1-2

4-20 mA

(default)