C.4.4 Grounding the Drive/Filter Assembly

Connect the drive/filter assembly to earth ground at the terminal provided next to the

filter’s AC input power terminals. The ground wire should be sized per EN-60204-1,
Part 5.2

1

,

for copper conductors and EN-60204-1, Part 8.2.2.2

2

, for non-copper

conductors. European Union standards require that the ground wire must be
green/yellow according to EN-60204-1, Part 15.2.2.

3

1

EN-60204-1, Part 5.2: Minimum Cross-Sectional Area of the External Protective

Copper Conductor

2

EN-60204-1, Part 8.2.2.2: Protective Conductors

Copper conductor should be used. If a material other than copper is used, its electrical

resistance per unit length should not exceed that of copper. Non-copper conductors
should not be less than 16 mm

2

in cross-sectional area.

3

EN-60204-1, Part 15.2.2: Identification of the Protective Conductor

For insulated conductors, the two-color combination of Green and Yellow should meet

the following criteria for any given 15 mm length: one of the colors should cover at

least 30% and no more than 70% of the surface, with the other color covering the

remainder of the surface.

Cross-Sectional Area of Phase

Conductors Supplying the Equipment

(S) (mm

2

)

Minimum Cross-sectional Area of the

External Protective Conductor (mm

2

)

S

≥ 16

S

16 < S

≤ 35

16

S

≥ 35

S/2