Troubleshooting the Drive

9-11

Table 9.1 - Resistance Checks (Continued)

200–400 HP Drives (with the motor connected)

IGBT

No.

Meter

Connection

(+) (-)

Component is OK if

resistance (R) is:

Component is defective if:

All

IGBTs

tested in

parallel

U/T3 *

10 < R < 1 Megohm

Continuity (short circuit) or

open when the meter is

connected with reversed

polarity

* U/T3
U/T3 **
* U/T3

* (+) DC Bus power terminal
** (-) DC Bus power terminal

200–400 HP Drives (with the motor disconnected)

IGBT

No.

Meter

Connection

(+) (-)

Component is OK if

resistance (R) is:

Component is defective if:

1

* W/T1

10 < R < 1 Megohm

Continuity (short circuit) or

open when the meter is

connected with reversed

polarity

2

* V/T2

3

* U/T3

4

W/T1 **

5

V/T2 **

6

U/T3 **

* (+) DC Bus power terminal
** (-) DC Bus power terminal