Mounting the Drive, Grounding, and Finding Wire Routing Locations

4-9

Figure 4.7 – Wire Routing Locations for 200-400 HP Drives

ALLOW 6 INCH RADIUS SERVICE LOOP

WITH INTERCONNECTION WIRING FROM

CONTROL BOARD WIRING TRAY TO

J1 CONNECTOR ON REGULATOR BOARD.

SIGNALS (VIA WIRING TRAY)

GROUND, A-C INPUT AND A-C OUTPUT TERMINALS

DANGER

OR LESS PRIOR TO SERVICING.

SLOTS SHOWN ABOVE. VOLTAGE MUST BE 50 VOLTS

VOLTAGE WITH A VOLTMETER THROUGH THE ACCESS

CAPACITORS TO DISCHARGE AND THEN CHECK THE

WAIT FIVE (5) MINUTES FOR THE D-C BUS

AFTER INPUT POWER HAS BEEN DISCONNECTED.

D-C BUS CAPACITORS RETAIN HAZARDOUS VOLTAGES

VOLTMETER TEST POINTS

+DC

-DC

!

BM

1FU

2FU

OR EQUIV.

2A

LITTLEFUSE

CLASS CC

TYPE MR

S

S

FU

E U F

E

E S

FU

UF

E

E

S

F UE

S

U

F

S

V/T2

(with Cover Removed)

DC-

807300-

142A

GND

DC+

U/T1

W/T3 R/L1

T/L3

S/L2

WIRING HARNESS 807300-138R

SIGNALS (VIA WIRING TRAY)

CONNECT USING 350MCM TWO HOLE TERMINAL LUGS

PULL SHIELD TABS IN AND ROTATE SHIELD OUT

GND

DANGER

TORQUE TO 325IN-LBS

DC+

DC-

U

V

W

R

POWER CONNECTIONS

W

IRI

NG
T

R

AY

S

T

VIEW FROM TOP