2-16

GV3000/SE AC Drive Hardware Reference, Version 6.06

Step 8. Verify that Terminal Strip Analog Input Offset (P.009), Terminal Strip Analog

Input Gain (P.010), and Terminal Strip Analog Input Configure (P.011) are

correctly set.

Note that the jumper settings must match the software settings otherwise the
reference value may differ from what is expected. Refer to the GV3000/SE

Software Start-Up and Reference manual for more information.

2.8.1.2 Setting the Analog Output Jumper (J17)

Jumper J17 is the analog output jumper. This jumper selects either a 0-10 VDC or

4-20 mA scaled signal output that is programmable to be proportional to either speed

or torque using parameter P.012. Refer to the GV3000/SE Software Start-Up and

Reference manual for more information on this parameter.

The jumper only selects a 0-10 VDC source voltage or 4-20 mA sink current to

represent speed or torque. Note that the 4-20 mA current selection requires a power

supply for operation as shown in tables 7.3 and 7.8, terminals 10 and 11.
Use the following procedure to set jumper J17:

Step 1. Turn off input power to the drive and wait five minutes.

Step 2. Remove the cover from the drive by unscrewing the four attaching screws.

On 200-400 HP drives, open the outer cabinet door.

Figure 2.12 – Jumper J4 Settings for Analog Input Speed Reference

J4

J4

10 VDC

Pins 2-3

Pins 1-2

0-20 mA

(default)

Voltage Input Option

Current Input Option

!

ATTENTION: DC bus capacitors retain hazardous voltages after input

power has been disconnected. After disconnecting input power, wait five

(5) minutes for the DC bus capacitors to discharge and then check the

voltage with a voltmeter to ensure the DC bus capacitors are discharged

before touching any internal components. Failure to observe this

precaution could result in severe bodily injury or loss of life.

!

ATTENTION: Do not operate 200-400 HP drives with the outer and inner

cabinet doors open due to possible exposure to high voltage. Close the

outer and inner cabinet doors before putting the drive into run. Failure to

observe this precaution could result in severe bodily injury or loss of life.