GV3000/SE AC Drive Hardware Reference, Version 6.06

Table 2.1 – Power and NEMA Enclosure Ratings

Model

Number

Selected

Regulation

1

and

Horsepower

Rating

1

With V/Hz regulation, 110% continuous output current capability. With vector regulation, 150% output current capability for one minute.

NEMA

Rating

Input

KVA

Input

Amps

2

2

Input Voltage: 380-460 VAC (+/-10%)

Output

Amps

at

2 kHz

Output

Amps

at

4 kHz

Output

Amps

at

8 kHz

Power

Loss

Watts

(Full

Load)

1V4160

1V4460

V/Hz or Vector

(1 HP)

1

4X/12

2.0

2.5

2.1

2.1

2.1

60

2V4160

2V4460

V/Hz or Vector

(2 HP)

1

4X/12

3.3

4.2

3.4

3.4

3.4

100

3V4160

3V4460

V/Hz or Vector

(3 HP)

1

4X/12

5.1

6.4

5.3

5.3

5.3

140

5V4160

5V4460

V/Hz or Vector

(5 HP)

1

4X/12

7.9

9.9

8.2

8.2

8.2

180

7V4160

7V4260

V/Hz or Vector

(7.5 HP)

1

12

10.7

13.4

11.1

11.1

11.1

210

10V4160

10V4260

V/Hz or Vector

(10 HP)

1

12

13.4

16.8

14.2

14.2

14.2

250

15V4160

15V4260

V/Hz or Vector

(15 HP)

1

12

20.2

25.4

21.0

21.0

21.0

375

20V4160

20V4260

V/Hz or Vector

(20 HP)

1

12

26.1

32.7

27.0

27.0

27.0

600

25G4160

25G4260

V/Hz

(25 HP)

1

12

29.5

37.0

30.4

30.4

30.4

600

25V4160

25V4260

V/Hz or Vector

(25 HP)

1

12

30.2

38.0

34.5

34.5

34.5

750

30V4160

30V4260

V/Hz or Vector

(30 HP)

1

12

35.0

44.0

39.0

39.0

39.0

800

40V4160

40V4260

V/Hz or Vector

(40 HP)

1

12

46.2

58.0

54.0

54.0

54.0

960

50V4160

50V4260

V/Hz or Vector

(50 HP)

1

12

57.3

72.0

67.0

67.0

67.0

1200

50R4160

50T4160

Vector (50 HP) or

V/Hz (75 HP)

1

65.0

81.0

81.0

102

70.0

90.0

56.0

72.0

41.0

54.0

1420

60G4160

60G4260

V/Hz

(60 HP)

1

12

71.7

90.0

78.0

78.0

78.0

1200

75R4160

75T4160

Vector (60-75 HP)

or V/Hz (100 HP)

1

80.0

100

101

126

89.0

116

71.0

93.0

53.0

70.0

1400

1780

125R4160

Vector (100-125 HP)

or V/Hz (125-150 HP)

1

127

170

159

213

152

210

122

168

91.0

126

2410

3200

200V4160

200V4160DS

3

3

With optional input disconnect factory installed

Vector (150-200 HP)

or V/Hz (200 HP)

1A

224

281

240

240

-

3290

250V4160

250V1460DS

3

V/Hz or Vector

(250 HP)

1A

269

337

302

302

-

4160

300V4160

300V4160DS

3

V/Hz or Vector

(300 HP)

1A

310

389

361

361

-

5100

350V4160

350V4160DS

3

V/Hz or Vector

(350 HP)

1A

352

442

414

414

-

6150

400V4160

400V4160DS

3

V/Hz or Vector

(400 HP)

1A

394

494

477

477

4

4

110% overload only at 4KHz in V/Hz and vector modes.

-