Rockwell Automation GV3000/SE AC Drive Ver. 6.06 Hdwe Ref., Installation, and Troubleshooting Manual User Manual

Page 74

Advertising
background image

7-10

GV3000/SE AC Drive Hardware Reference, Version 6.06

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring Analog Outputs

10

11

0-10 VDC or 4-20 mA

Analog Output Reference

Regulator Common

The setting of parameter P.012 selects the terminal strip

analog output source (either speed or torque). Jumper J17

must also be set. See figure 2.13.
The 4-20mA current selection requires a power supply for

operation. The power can be sourced from the encoder

supply, terminal 4 (15VDC), or from an external 15V power

supply. Note that the maximum supply current from terminal

4 is 250mA (encoder and current source) at 15V.
On the 1-60 HP and 200-400 HP Regulator boards, terminals

9 and 11 are internally connected.

Terminal

Strip

+

-

+

-

+

-

Load

(Meter or Analog Input)

Connection to the negative side of the

power supply is only required

when an external 15V power supply is used.

Advertising