T9300 base unit specification – Rockwell Automation AADvance Controller Solutions Handbook User Manual
Page 103

Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:
7-9
The bus and power connections from the processor base unit enter the backplane at
the left connector and are routed direct to the module connectors. The backplane
provides a connector at the right for the next I/O backplane. The connection to the
left of the backplane can connect to a processor base unit or another I/O base unit.
Adjacent base units clip together and are held in position by a plastic retaining clip.
Alternatively rows of I/O base units can be connected together using a T9310
expansion cable assembly.
T9300 Base Unit Specification
Table 23:
9300 Base Unit Specification
Attribute
Value
Electrical Specification
Supply voltage requirements
Redundant + 24V dc nominal; 18V dc to 32V
dc range (from Processor Base unit)
Physical Specification
Number of I/O modules supported
1, 2 or 3
Command busses
One
Response busses
24
Buses per system
2
Base units per bus
8
I/O Modules per bus
24 individual modules (not counting grouping)
(e.g. 12 dual or 8 triple module groups)
Mechanical Specification
Dimensions (height × width × depth)
235mm x 126mm
(9 1/4 in x 5 in)
Weight
133g (5 oz.)