Triple Modular Redundant Channel Capacity

When you need input modules arranged in triple modular redundant formations, each

group of three modules will share a single triple termination assembly and occupies a
whole I/O base unit. A single controller supports 16 groups of three modules, so a

hypothetical controller using 16-channel input modules and needing no output channels

would have a capacity of 16 x 16 = 256 input channels.
A solution using 8-channel modules and needing dual output modules as well as

triplicated input modules would, with a ratio of 2:1 of inputs to outputs, provide 96

input channels and 48 output channels. These capacities are derived like this:

Input Channels

12 groups of three 8-channel input modules occupy 12 base units and yield 12 x 8

= 96 input channels.

Output Channels

6 pairs of output modules occupy the remaining 4 base units and yield 6 x 8 = 48

output channels.