Rockwell Automation AADvance Controller Solutions Handbook User Manual

Page 29

Advertising
background image


Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:

1-17

Note: The CIP Protocol is intended to allow AADvance users to exchange data

between AADvance controllers and the Allen Bradley Logix family controllers, using
produce/consume messaging. Produce/Consume messaging does not support

downloading to or for monitoring AADvance controllers. It is not recommended to

use the CIP network to exchange data between AADvance controllers unless this is
exclusively for non-safety data. The SNCP network should be used for Safety related

data exchange between AADvance Controllers (see SNCP and variable Bindings in this
publication).

HART

The AADvance controller supports utilizing dedicated HART modems on each

analogue input and output channel allowing HART field device status, diagnostics and
process data to be integrated into the application logic, thus increasing the level of SIF

diagnostics significantly.
The AADvance analogue input/output modules use HART commands #03 to collect
data from the field device as defined by Revision 5 of the HART specification. The

application can be configured to use HART information to monitor and respond to

device conditions. It may also be used to provide diagnostic information such as

comparison and error reporting.
An additional feature of the AADvance controller is that it also combines with the

AADvance DTM to enable asset management software (ASM) to communicate with

HART devices.

Note: The AADvance system does not alter the messages passed between the asset
management software and the field device and acts as a transport mechanism only.

AADvance HART Features

Provides passthru support for HART Standards 5, 6 and 7.

Variables can be configured for each Analogue input and output channel to

monitor HART device information.

HART support is available on each Analogue Input or Output channel.

AADvance uses a single dedicated Ethernet port for HART passthru

communication.

Supports the AADvance DTM provided by Rockwell Automation.

A typical HART set up is shown below:

Advertising