Table 14:

Output Modules


Modules

TÜV Certified
Configuration

Conditions

Digital Outputs

T8451, 24V dc, 8
channel.

+

T9851/2 TA,24V dc,
8 Channel,

Simplex/Dual

1oo1D, 1oo2 or

2oo2D

De-energize to action (normally energized): SIL3

with 1 or 2 modules fitted. 2oo2D with dual output
modules fitted.

Energize to action (normally de-energized): SIL2

with 1 module fitted and SIL3 with 2 modules fitted.

Note: Faulty modules must be repaired or replaced

within the MTTR assumed for the PFD calculations
for energize-to-action applications.

Table 15:

Auxiliary Modules

Modules

Conditions

Processor Base

T9100

Safety-related and can be used for safety critical applications in Fault
tolerant/High demand SIL2 applications with 2 modules fitted or

SIL3 applications with 2 or 3 modules fitted.

I/O Base

T9300 (3-way)

Safety-related and can be used for safety critical applications in SIL3.

Note: Revisions of modules are subject to change. A list of the released versions is
held by TÜV or can be obtained from Rockwell Automation.