Single input modules are designed to meet SIL3 and in the most basic simplex
configuration they offer a fail-safe solution. The AADvance system has comprehensive

built-in diagnostics, while maintenance activities are straight forward operations which

maximize system availability.
The AADvance controller is developed and built for IEC 61131 compliance and

includes support for all five programming languages. Program access is secured by a

removable "Program Enable" key. Simulation software lets you prove a new application

before reprogramming and downloading, again maximizing system uptime.

Performance and Electrical Specifications

Table 1:

Performance and Electrical Specifications

Attribute

Value

Functional Characteristics

Number of processor modules

1 (non-safety applications, SIL1 and SIL2 safety
applications)

2 (SIL3 applications)

3 (SIL3 fault tolerant and TMR applications)

Maximum number of I/O modules

48 modules (16 base units) - Two I/O busses each

holds 24 modules (8 I/O base units)

External interfaces

Network (10/100BASE-TX Ethernet)
Serial data communications (RS-485)

Inter-controller links

High integrity communications using Safety Network

Control Protocol (SNCP)

Application software support

All IEC 61131 languages

Displays

Status LEDs on each module

User controls

Fault Reset button on each processor module

Security

Plug-in "Program Enable" key for access to application

project and system configuration tools.

Mounting

DIN rail or flat panel

Performance Characteristics

Safety integrity level

IEC 61508 SIL2
IEC 61508 SIL3
(depending on processor and I/O module

configuration)

Sequence of Event

Processor Module (for internal
variables)

Event Resolution
Time Stamp Accuracy

Digital Input Module

Event Resolution

1ms
Application Scan

1ms