Solutions handbook (aadvance controller) – Rockwell Automation AADvance Controller Solutions Handbook User Manual

Page 18

Advertising
background image

1-6

Document: 553631

(ICSTT-RM447J_EN_P) Issue: 09:

Solutions Handbook (AADvance Controller)


Functional Stress

5Hz to 9Hz

Continuous

1.7mm amplitude

Occasional

3.5mm amplitude

Withstand

10Hz to 150Hz

Acceleration

0.1g in 3 axes

Endurance

10Hz to 150Hz

Acceleration

0.5g in 3 axes

Shock

15g peak, 11ms duration, ½ sine

Altitude

Operating

0 to 2000m (0 to 6,600 ft.)

Storage and Transport

0 to 3000m (0 to 10,000 ft.)

This equipment must not be transported in
unpressurized aircraft flown above 10,000 ft.

Electromagnetic Interference

Tested to the following standards: EN 61326-

1:2006, Class A; EN 61326-3-1:2008, EN 54-4:
1997, A1; EN 61131-2:2007; EN 62061:2005.

Hazardous Location Capability

Suitable for Class I Div 2 and Zone 2

Note:

Casing: Standard AADvance modules also have a plastic casing and are rated IP20:
Protected against solid objects over 12mm (1/2in.) for example "fingers". There is no
specific protection against liquids.