Solutions handbook (aadvance controller) – Rockwell Automation AADvance Controller Solutions Handbook User Manual
Page 18

1-6
Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)
Functional Stress
5Hz to 9Hz
Continuous
1.7mm amplitude
Occasional
3.5mm amplitude
Withstand
10Hz to 150Hz
Acceleration
0.1g in 3 axes
Endurance
10Hz to 150Hz
Acceleration
0.5g in 3 axes
Shock
15g peak, 11ms duration, ½ sine
Altitude
Operating
0 to 2000m (0 to 6,600 ft.)
Storage and Transport
0 to 3000m (0 to 10,000 ft.)
This equipment must not be transported in
unpressurized aircraft flown above 10,000 ft.
Electromagnetic Interference
Tested to the following standards: EN 61326-
1:2006, Class A; EN 61326-3-1:2008, EN 54-4:
1997, A1; EN 61131-2:2007; EN 62061:2005.
Hazardous Location Capability
Suitable for Class I Div 2 and Zone 2
Note:
Casing: Standard AADvance modules also have a plastic casing and are rated IP20:
Protected against solid objects over 12mm (1/2in.) for example "fingers". There is no
specific protection against liquids.