Ethernet, Serial Data and Power Connections

The external connections for Earthing, Ethernet (E1-1 to E3-2), serial data (S1-1 to

S3-2) and the +24V dc Redundant powers supplies (PWR-1 and PWR-2) are all
located on the T9100 Processor Base Unit. There are two serial data and two

Ethernet connectors for each processor module. Two connectors for the dual

redundant power supplies, a stud for the Earth and a connector for the security device
(KEY) also known as the Program Enable Key.

Note: The FLT connector is not used.

Serial Communications

The serial ports (S1-1 & S1-2, S2-1 & S2-2, S3-1 & S3-2) support the following

signal modes depending upon use:

RS485fd: A four-wire full duplex connection that features separate busses for
transmit and receive. This selection should also be used when the controller is

acting as a Modbus master using the optional four-wire definition described in

Section 3.3.3 of the Modbus-over-serial standard.

RS485fdmux: A four-wire full-duplex connection with tri-state outputs on the
transmit connections. This should be used when the controller is acting as a

Modbus slave on a four-wire bus.

RS485hdmux: A two-wire half duplex connection appropriate for or master slave

or slave use. This is shown in the Modbus-over-serial standard.