Choosing termination assemblies, Specify i/o base units – Rockwell Automation AADvance Controller Solutions Handbook User Manual

Page 91

Advertising
background image


Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:

6-5

Choosing Termination Assemblies

The use of termination assemblies gives the AADvance system exceptional flexibility
for creating different architectures and expanding the system. Each termination

assembly is a very simple circuit that is matched to a type of I/O module and to a

particular module configuration. This table shows a summary of the termination
assemblies which are available and the associated I/O module configurations.

Table 17:

Choosing a Termination Assembly

Simplex I/O Module

Configuration

Dual I/O Module

Configuration

Triple I/O Module

Configuration

Digital input

T9801, Digital Input
TA, 16 channel,

Simplex Commoned
(non-isolated)

T9802, Digital Input
TA, 16 channel,

Dual

T9803, Digital Input
TA, 16 channel, Triple

Analogue input

T9831, Analogue Input
TA, 16 channel,

Simplex, commoned
(non-isolated)

T9832, Analogue
Input TA, 16

channel, Dual

T9833, Analogue Input
TA, 16 channel, Triple

Digital output

T9851, Digital Output

TA, 8 channel, Simplex,
commoned
(non-isolated)

T9852, Digital

Output TA, 8
channel, Dual
(non-isolated)

Not applicable

Analogue Output

T9881, Analogue

Output TA, 8 Channel,
Simplex, commoned

T9882, Analogue

Output TA, 8
channel, Dual

Not applicable

IMPORTANT: The termination assemblies for inputs accommodate 8-channel I/O

modules and 16-channel I/O modules. A dual or triple arrangement can be made of 8-
or 16-channel modules, but not a mixture of the two.

You need one termination assembly for each group of associated modules. For
example:

Four T9401 digital input modules used in two, dual redundant configurations need

two T9802 termination assemblies — one for each pair of modules

Four T9401 digital input modules used for simplex inputs need four T9801

termination assemblies — one for each module

Specify I/O Base Units

The T9300 I/O base unit (3 way) is a single, standardized design which suits all

termination assemblies and I/O modules. The base unit can accommodate one triple
modular redundant assembly, one dual assembly and one simplex assembly or up to

three to simplex assemblies. The dual and triple modular redundant assemblies can

bridge adjacent base units, so two base units can (for example) hold three dual
assemblies.