SIL2 Fail-safe Architecture

The following is a simplex fail-safe SIL2 architecture, where I/O modules operate in

1oo1D under no fault conditions and will fail-safe on the first detected fault. The
processor module operates in 1oo1D and will degrade to fail safe on the first detected

fault.

Note: A simplex configuration can only be used for "low demand"

Table 5:

Modules for SIL2 Fail-Safe Architecture

Position

Module Type

I/P A

T9401/2 Digital Input Module, 24V dc, 8/16 Channel +

T9801 Digital Input TA, 16 Channel, Simplex. or

T9431/2 Analogue Input Module,

8/16 Channel +

T9831 Analogue Input TA, 16 Channel, Simplex

T9300 I/O Base Unit

CPU A

1 x T9110 Processor Module, T9100 Processor Base

Unit,

O/P A

T9451 Digital Output Module, 24V dc, 8 Channel,
isolated +

T9851 Digital Output TA, 24V dc 8 Channel, Simplex