5-2

Document: 553631

(ICSTT-RM447J_EN_P) Issue: 09:

Solutions Handbook (AADvance Controller)


Simplex I/O Channel Capacity

When you need I/O modules arranged in only simplex configurations you should use

the simplex termination assembly for each module type. You can use any physical
arrangement of 8-channel and 16-channel input modules with their simplex termination

assemblies, also any arrangement of output modules with simplex termination

assemblies. For example, you might place all digital inputs together in a rack and all
analogue inputs together, or mix them together.
The maximum number of simplex I/O channels is limited only by the choice of

modules. For example, 16 x 16 Channel input modules and 32 x 8 Channel output
modules, equals a maximum of 512 channels