Dissipation – Rockwell Automation AADvance Controller Solutions Handbook User Manual

Page 93

Advertising
background image


Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:

6-7

Estimate Module Supply Power Dissipation and Field Loop Power Dissipation

Module supply voltage and field power consumption is dissipated as heat. Use these

tables to estimate the supply voltage and field power heat dissipation of your system.

Note: All figures given are worst-case estimates based upon maximum operating field
current and voltages.

Table 19:

Estimating Module Supply Power Dissipation

Item

Number
of

Modules

Power Dissipation

Subtotal
(W/BTU/hr)

T9110 Processor Module

× 8.0W (27.3BTU/hr) =

T9401 Digital Input Module 24V dc, 8 channel

× 3.3W (11.3BTU/hr) =

T9402 Digital Input Module 24V dc, 16 channel

× 4.0W (13.6BTU/hr) =

T9431 Analogue Input Module, 8 channel

× 3.3W (11.3BTU/hr) =

T9432 Analogue Input Module, 16 channel

× 4.0W (13.6BTU/hr) =

T9451 Digital Output Module, 24V dc, 8 channel

× 3.0W (10.2BTU/h) =

T9482 Analogue Output Module, 8 channel, isolated

× 3.6W (12.3BTU/hr) =

Total:

Table 20:

Estimating Field Loop Power Dissipation

Item

Number

of Field
loops

Maximum Field

Loop Power
Dissipation

Subtotal

(W/BTU/hr)

T9801/2/3 Digital Input Termination Assembly (powered by
the T9401/2 module)

× 0.2W (0.68BTU/hr) =

T9831/2/3 Analogue Input Termination Assembly (powered
by the T9431/2 module)

× 0.08W
(0.27BTU/hr)

=

T9451 Digital Output Module, 24V dc, 8 channel (1A load)

x 0.57W (1.94
BTU/hr)

=

T9482 Analogue Output Module, 8 channel, isolated

× 0.77W
(2.63BTU/hr)

=

Total:


Advertising