SIL2 Output Architecture

A SIL2 output architecture has a single output module with single processor and single

or redundant input modules.

In de-energize to trip operation, the output modules operate in 1oo2D no fault

conditions and degrade to 1oo1D on detection of the first fault in either module

and fail-safe when there are faults on both output modules.

In energize to action operation, the output module operates in 1oo2D under no
fault conditions, degrade to 1oo1D on the detection of the first fault in either

module, and they fail-safe when there are faults on both modules.

The illustration shows a SIL2 single output arrangement where the output and

processor modules operate in 1oo1D under no fault conditions and will fail-safe on the
first detected fault.

Table 7:

Modules for SIL2 Fault Tolerant Output Architecture

Position

Module Type

I/P A

T9401/2 Digital Input Module, 24V dc, 8/16 Channel. +
T9801 Digital Input TA, 16 Channel, Simplex

or

T9431/2 Analogue Input Module, 8/16 Channel +
T9831 Analogue Input TA, 16 Channel, Simplex

T9300 Base Unit

CPU A

1 x T9110 Processor Module, T9100 Processor Base Unit
and 9300 I/O Base Unit

O/P A

1 × T9451 Digital Output Module, 24V dc, 8 Channel +

T9851 Digital Output TA, 24V dc, 8 Channel, Dual