Planned certified configurations – Rockwell Automation AADvance Controller Solutions Handbook User Manual

Page 61

Advertising
background image


Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:

2-11

CPU A &

CPU B

3 × T9110 Processor Module, T9100 Processor Base Unit,

O/P A

2 × T9451 Digital Output Module, 24V dc, 8 Channel +
9852 Digital Output TA, 24V dc 8 Channel, Dual

Note: All configurations that use dual or triplicate processor modules are suitable for

SIL3 architectures with de-energize to trip outputs. Dual outputs are also required for
SIL3 energize to action outputs.

Planned Certified Configurations

Table 12:

Central Modules

Modules

TÜV Certified
Configuration

Conditions

Processor Module
T9110

1oo1D, 1oo2D,
2oo3D

Safety-related and can be used for safety-critical
applications in SIL2 with 1 module fitted and SIL3
applications with 2 or 3 modules fitted.

Note: For High Demand applications you must use
a minimum of two processors.

Table 13:

Input Modules

Modules

TÜV Certified

Configuration

Conditions

Digital Inputs
T9401/2, 24V dc,

8/16 Channel,
isolated.

+

T9801/2/3 Digital
Input TA, 16 channel,
Simplex/Dual/TMR

1oo1D, 1oo2D,
2oo3D

Within a specified safety accuracy limit of 1.0V dc.
De-energized to action (normally energized): SIL3

with 1, 2 or 3 modules fitted.

Energize to action (normally de-energized): with 1, 2
or 3 modules fitted

Note: when the integrity level is at 1oo1D then the
faulty module must be replaced to restore the
integrity level back to 1oo2D.

Analogue Inputs
T9431/2, 8/16
Channel, isolated

+

T9831/2/3 Analogue
Input TA, 16

Channel,
Simplex/Dual/TMR

1oo1D, 1oo2D,
2oo3D

Within the manufactures specified safety accuracy
limits of 200µA. The safety state of the analogue
input has to be set to a safe value which is a

calculated value based on a count value of 0mA.
(refer to the AADvance Configuration Guide Doc
no: 553633 for more details)

SIL3 with 1, 2 or 3 modules fitted.

Note: when the integrity level is at 1oo1D then the
faulty module must be replaced within the MTTR

assumed for the PFD calculations to restore the
integrity level back to 1oo2D.