1-18

Document: 553631

(ICSTT-RM447J_EN_P) Issue: 09:

Solutions Handbook (AADvance Controller)


Figure 1: Example HART Pass-through System

SNCP Safety Networks

SNCP (Safety Network Control Protocol) is the Safety Protocol that allows

elements of an AADvance System to exchange data. AADvance SNCP is a SIL 3

certified protocol which provides a safety layer for the Ethernet network making it a

"Black Channel". Data is exchanged by creating a relationship between variables in
different AADvance controllers; this is called "Binding Variables". Once variables are

bound between controllers the SNCP protocol provides a transparent SIL 3 Certified

layer allowing safety related data to be passed between AADvance controllers.
The bindings are based on a producer/consumer model. The controller consuming the

data establishes a binding link with the Controller producing the data, and manages the

entire exchange of data, including scheduling the data exchange, providing the
diagnostics, managing the safety response in the event of faults and managing the

communications redundancy.
SNCP Networks can be configured as Simplex (Fail Safe) or Redundant (Fault tolerant),

the choice of network configuration is dependent on the applications safety and
availability requirements. The data exchange is independent of the physical; network

configuration as the connection between the controllers is treated as a logical

network.