Rockwell Automation AADvance Controller Solutions Handbook User Manual

Page 23

Advertising
background image


Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:

1-11

The AADvance controller has also been evaluated under certificate IECEx UL
12.0032X to the standards IEC 60079-0; (5

th

Edition) and IEC 60079-15 (4

th

Edition).


[ certificate to be supplied]

For a system that is located in a Zone 2 Hazardous environment where ATEX

certification is required, all modules should be installed in an ATEX and IECEx

Certified, tool accessible IP54 enclosure. The enclosure is to be marked with the

following: "Warning - Do not open when energized". After installation of the modules
into the enclosure, access to termination compartments shall be dimensioned so that

conductors can be readily connected. The modules and assemblies are for use in an

area of not more than pollution degree 2 in accordance with IEC 60664-1

Module label