Error and Informational Messages
140
Message
16-May-06 17:38:06
PItoPI 1> One of the required Failover Synchronization
points was not loaded.
Error = 0: The Heartbeat point for this copy of the
interface was not loaded.
The input Historian tag was not loaded
Cause
The Heartbeat tag is not configured properly.
Resolution
Check validity of point attributes. For example, make sure Location1 attribute is valid
for the interface. All failover tags must have the same PointSource and Location1
attributes. Modify point attributes as necessary and restart the interface.
Message
17-May-06 09:06:03
PItoPI > The Uniint FailOver ID (/UFO_ID) must be a
positive integer.
Cause
The UFO_ID parameter has not been assigned a positive integer value.
Resolution
Change and verify the parameter to a positive integer and restart the interface.
Message
17-May-06 09:06:03
PItoPI 1> The Failover ID parameter (/UFO_ID) was found
but the ID for the redundant copy was not found
Cause
The
/UFO_OtherID
parameter is not defined or has not been assigned a positive
integer value.
Resolution
Change and verify the
/UFO_OtherID
parameter to a positive integer and restart
the interface.