Error and Informational Messages

140

Message

16-May-06 17:38:06
PItoPI 1> One of the required Failover Synchronization
points was not loaded.
Error = 0: The Heartbeat point for this copy of the
interface was not loaded.
The input Historian tag was not loaded

Cause

The Heartbeat tag is not configured properly.

Resolution

Check validity of point attributes. For example, make sure Location1 attribute is valid
for the interface. All failover tags must have the same PointSource and Location1
attributes. Modify point attributes as necessary and restart the interface.

Message

17-May-06 09:06:03
PItoPI > The Uniint FailOver ID (/UFO_ID) must be a
positive integer.

Cause

The UFO_ID parameter has not been assigned a positive integer value.

Resolution

Change and verify the parameter to a positive integer and restart the interface.

Message

17-May-06 09:06:03
PItoPI 1> The Failover ID parameter (/UFO_ID) was found
but the ID for the redundant copy was not found

Cause

The

/UFO_OtherID

parameter is not defined or has not been assigned a positive

integer value.

Resolution

Change and verify the

/UFO_OtherID

parameter to a positive integer and restart

the interface.