Installation Checklist

28

9. Build input tags and, if desired, output tags for this Interface. Important point

attributes and their use are:

Location1

specifies the interface instance ID

Location2

specifies for timestamp adjustment.

Location3

specifies for configuring interface status events.

Location4

specifies the scan class.

Location5

sets the write mode of archived data on the receiving Historian Server.

InstrumentTag

specifies the name of the Source Tag from the Source Historian

Server.

ExDesc

is an alternative way to specify the Source Tag. This can be specified with

STAG=<tagname>

.

UserInt1

defines Source Tag point ID instead of using source tag name.

10. Start the interface interactively and confirm its successful connection to the Historian

Server without buffering.

11. Confirm that the interface collects data successfully.

12. Stop the interface and configure a buffering application (either Bufserv or PIBufss).

When configuring buffering use the ICU menu item Tools  Buffering… 
Buffering Settings to make a change to the default value (32678) for the Primary and
Secondary Memory Buffer Size (Bytes) to 2000000. This will optimize the
throughput for buffering and is recommended by OSIsoft.

13. Start the buffering application and the interface. Confirm that the interface works

together with the buffering application by either physically removing the connection
between the interface node and the Historian Server Node or by stopping the
Historian Server.

14. Configure the interface to run as a Service. Confirm that the interface runs properly

as a Service.

15. Restart the interface node and confirm that the interface and the buffering application

restart.

Interface Diagnostics

1. Configure Scan Class Performance points.

2. Install the Historian Performance Monitor Interface (Full Version only) on the

interface node.

3. Configure Performance Counter points.

4. Configure UniInt Health Monitoring points

5. Configure the I/O Rate point.

6. Install and configure the Interface Status Utility on the Historian Server Node.

7. Configure the Interface Status point.