UniInt Failover Configuration

76

Quick Overview

The Quick Overview below may be used to configure this Interface for failover. The failover
configuration requires the two copies of the interface participating in failover be installed on
different nodes. Users should verify non-failover interface operation as discussed in the

Installation Checklist

section of this manual prior to configuring the interface for failover

operations. If you are not familiar with UniInt failover configuration, return to this section
after reading the rest of the

UniInt Failover Configuration

section in detail. If a failure occurs

at any step below, correct the error and start again at the beginning of step 6 Test in the table
below. For the discussion below, the first copy of the interface configured and tested will be
considered the primary interface and the second copy of the interface configured will be the
backup interface.

Configuration

One Data Source

Two Interfaces

Prerequisites

Interface 1 is the Primary interface for collection of FactoryTalk Historian data from

the data source.

Interface 2 is the Backup interface for collection of FactoryTalk Historian data from

the data source.

You must set up a shared file.

Phase 2: The shared file must store data for five failover tags: (1) Active ID,

(2) Heartbeat 1, (3) Heartbeat 2, (4) Device Status 1 and (5) Device Status 2.

Each interface must be configured with two required failover command line

parameters: (1) its FailoverID number (

/UFO_ID

); (2) the FailoverID number of its

Backup interface (

/UFO_OtherID

). You must also specify the name of the Historian

Server host for exceptions and Historian tag updates.

All other configuration parameters for the two interfaces must be identical.