FactoryTalk Historian To Historian Interface User Guide

69

.BAT

.INI

Description

/stopstat

or

/stopatat=
digstate

Default:

/stopstat=
"Intf shut"

Optional

--

If the

/stopstat

parameter is present on

the startup command line, then the
digital state

Intf Shut

will be written to

each Historian Point when the interface is
stopped.
If

/stopstat=digstate

is present on

the command line, then the digital state,

digstate

, will be written to each Historian

Point when the interface is stopped. UniInt
uses the first occurrence in the table.
If neither

/stopstat

nor

/stopstat=digstate

is specified on the

command line, then no digital states will be
written when the interface is shut down.
Note: The

/stopstat

parameter is

disabled If the interface is running in a UniInt
failover configuration as defined in the

UniInt

Failover Configuration

section of this manual.

Therefore, the digital state,

digstate

, will

not be written to each Historian Point when
the interface is stopped. This prevents the
digital state being written to Historian Points
while a redundant system is also writing data
to the same Historian Points. The

/stopstat

parameter is disabled even if

there is only one interface active in the
failover configuration.

Examples:

/stopstat=shutdown
/stopstat="Intf Shut"

The entire

digstate

value should be

enclosed within double quotes when there is
a space in

digstate

.

/ts

Optional

--

Suppress „IO Timeout‟ events when
reconnecting to source Historian Server.
These events are configured through

Location3

attribute.

If this switch is not set, the event written at
reconnection will prevent history from being
recovered for the period of the disconnection.