Sample startup configuration files, Sample pitopi.bat file – Rockwell Automation FactoryTalk Historian SE 3.0 H2H Interface User Guide User Manual

Page 79

Advertising
background image

FactoryTalk Historian To Historian Interface User Guide

73

.BAT

.INI

Description

/sec_src=
node :port

Required

--

Name or IP address of the secondary source
Historian Server.

/sec_src=node_name:tcpip_port

The port number is 5450 (PI3). PI2 is not supported
for source Historian Server failover.

/ssu1=tag

Required

--

Historian Interface Status Utility tag name for the

/src_host

source Historian Server.

/ssu1=<tagname>

Required for monitoring source data quality (current
or stale data).

/ssu2=tag

Required

--

Historian Interface Status Utility tag name for the

/sec_src

source Historian Server.

/ssu2=<tagname>

Required for monitoring source data quality (current
or stale data).

Sample Startup Configuration Files

The startup files for the interface reside in the directory

PIHOME\Interfaces\PItoPI

where

PIHOME

is defined in

%WINDIR%\pipc.ini

by the installation program. Typically,

PIHOME

is

c:\pipc

. The startup files consist of

PItoPI.bat

and

PItoPI.ini

.

Sample PItoPI.bat File

REM===============================================================

REM

REM PItoPI.bat
REM
REM Sample startup file for the PItoPI TCP/IP Interface
REM
REM===============================================================
REM
REM Rockwell Automation strongly recommends using ICU to modify startup
files.
REM
REM Sample command line
REM
.\PItoPI.exe ^
/host=XXXXXX:5450 ^
/src_host=XXXXXX:5450 ^
/ps=PItoPI ^
/id=1 ^
/f=10

REM End of PItoPI.bat File