FactoryTalk Historian To Historian Interface User Guide

49

Chapter 7.

Interface Status Tag Configuration

The following procedure describes how to create and configure interface status tags. These
tags are created on the receiving Historian Server. See section

Interface Status Tags

for a

complete description of this functionality.

1. Create a digital state set for the status tag. The following tables display the digital

state set definitions.

Internal Status Tag:

Digital State

String

0

STARTUP

1

HISTORYRECOVERY

2

SCANNING

3

SHUTDOWN

4

ACCESSDENIED

5

SRCDISCONNECT

6

RCVDISCONNECT

Failover Status Tag:

Digital State

String

0

RECONNECTING

1

PRIMARY

2

FAILOVER

3

SECONDARY

2. Create a digital tag on the receiving Historian Server with the following attributes:

Attribute

Value

PointSource

L

PointType

Digital

Compressing

0

ExcDev

0

DigitalStateSet

As defined in the receiving
PI3 server digital state
database.