Chapter 7. interface status tag configuration, Chapter 7, Interface status tag configuration – Rockwell Automation FactoryTalk Historian SE 3.0 H2H Interface User Guide User Manual
Page 55

FactoryTalk Historian To Historian Interface User Guide
49
Chapter 7.
Interface Status Tag Configuration
The following procedure describes how to create and configure interface status tags. These
tags are created on the receiving Historian Server. See section
complete description of this functionality.
1. Create a digital state set for the status tag. The following tables display the digital
state set definitions.
Internal Status Tag:
Digital State
String
0
STARTUP
1
HISTORYRECOVERY
2
SCANNING
3
SHUTDOWN
4
ACCESSDENIED
5
SRCDISCONNECT
6
RCVDISCONNECT
Failover Status Tag:
Digital State
String
0
RECONNECTING
1
PRIMARY
2
FAILOVER
3
SECONDARY
2. Create a digital tag on the receiving Historian Server with the following attributes:
Attribute
Value
PointSource
L
PointType
Digital
Compressing
0
ExcDev
0
DigitalStateSet
As defined in the receiving
PI3 server digital state
database.