6-10 ADS TRITON+ Manual
Enter the slave address number in the ID field to be used
when facilitating communication between the
TRITON+/ExPAC/XBUS and the third-party system (e.g.,
a SCADA system, RTU, or process control system).
Choose a number from 1 to 254, excluding the numbers 1,
58, and 97. For installations involving the Telog Ru-33,
ADS recommends using 55 as the slave ID.
Enter the amount of time, in milliseconds, following a
request you want the monitor to wait before returning the
requested data to the third-party system in the Delay
Response field. (This field typically does not need
editing.)
Click on the OK button.
10. Select the Save button to save the current parameters on the
dialog to the local directory or network.
11. Continue to enter the monitoring point information and assign
and edit the devices.
Configure the Monitoring Point(s)
The second step in configuring a monitor is entering the monitoring
point information. This involves designating the pipe
characteristics at the monitoring point and assigning and editing the
devices corresponding to the monitoring point.
The monitoring point represents the physical location at which the
sensors are installed in the pipe or channel. A monitor location can
support up to two monitoring points, and the settings must be
designated for each monitoring point.
Enter the information for each monitoring point in the following
way:
1. Select the type or shape of the pipe or channel in which the
sensors are installed from the Type drop-down list on the ADS
Qstart dialog.