ADS Environmental Services ADS TRITON+ QR 775027 A3 User Manual
Page 290

8-4
ADS TRITON+ Manual
Following are some common connection points:
Inside the transmitter that supplies the signal
SCADA I/O termination panel
PLC analog I/O terminals
RTU analog I/O terminals
Strip chart recorder I/O terminals
Integrator/totalizer I/O terminals
Front panel display I/O terminals
2. Configure the Analog Input 1 (or 2) component of the XIO
Device through Qstart with the analog input parameters that
indicate the values or measurements that correspond to the
analog signals within the 4-20mA range and the specific kind of
data you want the monitor to store. Refer to Chapter 6,
Configuration and Activation, for instructions on supplying this
information in Qstart.
3. Connect the analog input wires to the ADS XIO in the
following way:
Note: Make sure the power is turned off to the third-party
device and XIO.
Release the latches and open the clear, front door on the
XIO.
Run the wires up through the left cable gland on the XIO
into the enclosure. ADS recommends using 18-gauge
wiring. You may need to loosen the plastic nut on the
cable gland on the outside of the XIO to feed the wires
through.