Analog and digital i/o 8-15 – ADS Environmental Services ADS TRITON+ QR 775027 A3 User Manual
Page 301

Analog and Digital I/O 8-15
I/O TERMINAL BLOCK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1
2
1
2
I1
I2
R1
R2
+ -
+ -
+ -
+ -
NC
4-20 mA
Analogue
Outputs
4-20 mA
Analogue
Inputs
Digital
(Switch)
Inputs
Digital
(Relay)
Outputs
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
DIGITAL INPUT TERMINALS
Term 9 Wire
Term 10 Wire
Connecting the 2 wires from the third-party device to Terminals 9 and 10
(digital input terminals) on the I/O terminal block
Connect the other ends of the wires to the third-party
device based on the vendor’s specifications.
Close and latch the door to the XIO.
3. Restore power to the customer’s device and the ADS XIO.
4. Test the digital inputs in the following way:
Make sure the monitor is activated with the appropriate
digital input parameters.
Allow the monitor to record data from the digital input for
at least two intervals in an inactive state and two intervals
in an active state.
Collect the data from the monitor.
Verify that the data accurately represents the states of the
inputs corresponding to the date/time stamps.