EVCO EPH4EXP Hardware manual User Manual

Page 106

Advertising
background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 106 of 116

The maximum lengths of the connecting cables are the followings:

power supply controller: 30 m (98 ft)

analog inputs: 100 m (328 ft), but AI6, AI7 and AI8 of c-pro 3 mega+ (10 m, 32 ft)

power supply transducers: 10 m (32 ft)

digital inputs: 100 m (328 ft), but DI8, DI9, DI10, DI11 and DI12 of c-pro 3 mega+

(10 m, 32 ft)

PWM analog output: 1 m (3.280 ft)

0-20 mA / 4-20 mA / 0-10 V analog outputs: 30 m (98 ft), but AO4 and AO5 of

c-pro 3 mega+ (10 m, 32 ft)

digital outputs (electromechanical relays): 100 m (328 ft), but DO9 and DO10 of

c-pro 3 mega+ (10 m, 32 ft)

RS-485 ports: 1,000 m (3,280 ft); also look at the Manuale Modbus specifications

and implementation guides

MP-Bus port: 10 m (32 ft)

CAN ports:

-

1,000 m (3,280 ft) with baud rate 20,000 baud

-

500 m (1,640 ft) with baud rate 50,000 baud

-

250 m (820 ft) with baud rate 125,000 baud

-

50 m (164 ft) with baud rate 500,000 baud

power supply user interface: 30 m (98 ft).

One suggests using the

connecting

kit

CJAV15

(female extractable screw

terminal

blocks

pitch

5.0 mm, 0.196 in; to order

separately).

For c-pro 3 mega and for

c-pro 3 NODE mega one

suggests

using

the

connecting kit CJAV16, for

c-pro

3

mega+

one

suggests

using

the

connecting

kit

CJAV21

(female extractable screw

terminal

blocks

pitch

5.0 mm, 0.196 in; to order

separately).

One suggests using the

connecting

kit

CJAV15

(female extractable screw

terminal

blocks

pitch

5.0 mm, 0.196 in; to order

separately).

To program the controller one has to use the programming

kit EVIF20TUXI (TTL / USB isolated serial interface + TTL

cable 2.5 m, 8 ft long + USB cable 2 m, 6 ft long; to order

separately).

Working temperature:

from -10 to 55 °C (14 to 131 °F) for the built-in v ersions, from -20 to 55 °C (-4 to 131 °F) for

the blind versions.

Storage temperature:

from -30 to 70 °C (-22 to 158 °F).

Working humidity:

from 5 to 95% of relative humidity without condensate.

Pollution situation:

2.

Working altitude:

from 0 to 2,000 m (0 to 6591 ft).

Transport altitude:

from 0 to 3,048 m (0 to 10,000 ft).

Advertising
This manual is related to the following products: