MICRO-SWITCH

Micro-switch to:

-

plug in the terminations of the RS-485 ports (120

, 0.25 W); position micro-switch 1 on position ON to plug in the termination

of the first RS-485 port and micro-switch 2 on position ON to plug in the termination of the second RS-485 port (plug in the

termination of the first and of the last element of the network)

-

polarize the network of the second RS-485 port (560

, 0.25 W); position micro-switches 3 and 4 on position ON to polarize

the network of the second RS-485 port (the network must be polarized by an element of the network same).

-

plug in the termination of the CAN port (120

, 0.5 W); position micro-switch 4 on position ON to plug in the termination of the

CAN port (plug in the termination of the first and of the last element of the network).

CAN BUS

CAN port.

Terminal

Meaning

CAN +

signal +

CAN -

signal -

GND

ground

The maximum number of devices that can make a CAN network (32) depends on the bus load; the bus load depends on the baud rate

of the CANbus communication and on the kind of device in the network.

For example: a CAN network can be made of a programmable controller, of four I / O expansions and of four user interfaces

with baud rate 500,000 baud.

The maximum length of the connecting cables of the CAN port depends on the baud rate of the CANbus communication, as

follows:

-

1,000 m (3,280 ft) with baud rate 20,000 baud

-

500 m (1,640 ft) with baud rate 50,000 baud

-

250 m (820 ft) with baud rate 125,000 baud

-

50 m (164 ft) with baud rate 500,000 baud.

Connect the CAN port using a twisted pair.