EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 93 of 116

Parameters (1)

AI3

- - -

- - -

- - -

NTC

kind of probe analog input 3

PTC

= PTC probe

NTC

= NTC probe

0-20mA = 0-20 mA transducer

4-20mA = 4-20 mA transducer

0-5V

= 0-5 V ratiometric transducer

0-10V

= 0-10 V ratiometric transducer

PT1000 = Pt 1000 probe

Parameters (1)

AI Err Time

0

240

s

2

analog inputs time-out (after this time without

communication with an analog input, the

expansion signals the analog input error)

Parameters (1)

AO1

- - -

- - -

- - -

PWM

kind of signal analog input 1

PWM

= PWM (Pulse With Modulation)

Parameters (1)

AO2

- - -

- - -

- - -

0-10V

kind of signal analog input 2

0-20mA = 0-20 mA

4-20mA = 4-20 mA

0-10V

= 0-10 V

Parameters (1)

AO3

- - -

- - -

- - -

0-10V

kind of signal analog input 3

0-20mA = 0-20 mA

4-20mA = 4-20 mA

0-10V

= 0-10 V

Parameters (2)

[ press button

RIGHT to

show it ]

I/O Timeout

1

240

s

60

time-out of the CANbus communication for

the test of the remote values of the I / O

(after

this

time

without

CANbus

communication, the I / O of the expansion is

disabled)

Networks / CAN

Bus

MyNode

1

127

- - -

2

local (or of the expansion) CAN node

address

Networks / CAN

Bus

Master

- - -

- - -

- - -

YES

enabling the operation as master in a CAN

network

YES

= yes

Networks / CAN

Bus

Baud

- - -

- - -

- - -

20K

CANbus communication baud rate

20K

= 20,000 baud

50K

= 50,000 baud

125K

= 125,000 baud

500K

= 500,000 baud

Networks / CAN

Bus

NetworkNode

[ 1 ] 0

[ 32 ]

127

- - -

[ 1 ] 99

address of a remote (or of a device in the

network) CAN node; example for [ 1 ] 2:

[ 1 ]

= node

2

= node’s address