EVCO EPH4EXP Hardware manual User Manual

Page 63

Advertising
background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 63 of 116

Networks / CAN

Bus

[ press button

RIGHT to

show it ]

TSEG2

1

7

- - -

7

reserved

Networks / CAN

Bus

[ press button

RIGHT to

show it ]

SJW

0

3

- - -

0

reserved

Networks / CAN

Bus

[ press button

RIGHT to

show it ]

BTR(1)

1

15

- - -

15

reserved

Networks /

UART1 (1)

Address

1

247

- - -

1

local (or of the controller) Modbus node

address in a RS-485 network wired on the

RS-485 port

Networks /

UART1 (1)

Baud Rate

- - -

- - -

- - -

9600

Modbus communication baud rate in a

RS-485 network wired on the RS-485 port

1200

= 1,200 baud

2400

= 2,400 baud

4800

= 4,800 baud

9600

= 9,600 baud

19200

= 19,200 baud

28800

= 28,000 baud

38400

= 38,400 baud

57600

= 57,600 baud

Networks /

UART1 (1)

Parity

- - -

- - -

- - -

EVEN

Modbus communication parity in a RS-485

network wired on the RS-485 port

NONE

= no parity

ODD

= odd

EVEN

= even

Networks /

UART1 (1)

Stop

- - -

- - -

- - -

1 BIT

Modbus communication stop bit number in a

RS-485 network wired on the RS-485 port

1 BIT

= 1 bit

2 BIT

= 2 bit