polarize the network of the RS-485 port (560

, 0.25 W); position micro-switches 2 and 3 on position ON to polarize the

network of the RS-485 port (the network must be polarized by an element of the network same).

-

plug in the termination of the CAN port (120

, 0.5 W); position micro-switch 4 on position ON to plug in the termination of the

CAN port (plug in the termination of the first and of the last element of the network).

CAN BUS

CAN port.

Terminal

Meaning

CAN +

signal +

CAN -

signal -

GND

ground

The maximum number of devices that can make a CAN network (32) depends on the bus load; the bus load depends on the baud rate

of the CANbus communication and on the kind of device in the network.

For example: a CAN network can be made of a programmable controller, of four I / O expansions and of four user interfaces

with baud rate 500,000 baud.

The maximum length of the connecting cables of the CAN port depends on the baud rate of the CANbus communication, as

follows:

-

1,000 m (3,280 ft) with baud rate 20,000 baud

-

500 m (1,640 ft) with baud rate 50,000 baud

-

250 m (820 ft) with baud rate 125,000 baud

-

50 m (164 ft) with baud rate 500,000 baud.

Connect the CAN port using a twisted pair.

For the settings about the CAN port look at chapter 6 “CONFIGURATION”.

DIGITAL OUTPUTS

In c-pro 3 hecto.

Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).

Terminal

Meaning

CO1/2

common digital outputs 1 and 2

NO1

normally open contact digital output 1