EVCO EPH4EXP Hardware manual User Manual

Page 107

Advertising
background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 107 of 116

Ambient conformity:

ROHS 2002 / 95, WEEE 2002 / 96 / EC, REACH CE 1907 / 2006.

EMC conformity:

EN / IEC 60730-1 enclosure 16.

Power supply:

24 VAC (±15%), 50 / 60 Hz (±3 Hz), 30 VA max. isolated or 20... 40 VDC, 22 W max.

isolated, supplied by a class 2 circuit.

The devices incorporate a protection against the reversal of polarity.

If the controller is powered in direct current, one will not have to respect the polarity of the

power supply voltage.

Protect the power supply of:

c-pro 3 hecto and of c-pro 3 EXP hecto with a fuse rated 0.8A-T 250 V

c-pro 3 mega and c-pro 3 mega+ with a fuse rated 2.5A-T 250 V.

Overvoltage category:

III.

Consumption:

c-pro 3 hecto and c-pro 3

hecto+

c-pro 3 mega, c-pro 3

mega+ and c-pro 3 NODE

mega

c-pro 3 EXP hecto and

c-pro 3 EXP hecto+

10 VA max. if the controller

is powered in alternate

current; 6 W max. if the

controller is powered in

direct current.

30 VA max. se il controllore

viene alimentato in corrente

alternata; 22 W max. se il

controllore viene alimentato

in corrente continua.

10 VA max. if the expansion

is powered in alternate

current; 6 W max. if the

expansion is powered in

direct current.

Real time clock:

c-pro 3 hecto and c-pro 3

hecto+

c-pro 3 mega, c-pro 3

mega+ and c-pro 3 NODE

mega

c-pro 3 EXP hecto and

c-pro 3 EXP hecto+

incorporated (with SuperCap battery).

not available.

Drift:

to 30 s / month at 25 °C (77 °F).

Alarm buzzer:

c-pro 3 hecto and c-pro 3

hecto+

c-pro 3 mega, c-pro 3

mega+ and c-pro 3 NODE

mega

c-pro 3 EXP hecto and

c-pro 3 EXP hecto+

not availale.

incorporated (not availale in

the blind versions).

not availale.

Analog inputs:

c-pro 3 hecto

c-pro 3 mega and c-pro 3

NODE mega

c-pro 3 EXP hecto