EVCO EPH4EXP Hardware manual User Manual

Page 87

Advertising
background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 87 of 116

parameter available in read only modality

errors counter of the seventh Belimo device

Networks / MP

Bus Debug

[press button

RIGHT to

show it ] (5)

Dev8

parameter available in read only modality

operation status of the eighth Belimo device

0

= NotUsed

1

= NotExist

2

= ToConfig

3

= OffLine

4

= InConfig

5

= OnLine

parameter available in read only modality

errors counter of the eighth Belimo device

Networks /

UART1 (1)

Address

1

247

- - -

1

local (or of the controller) Modbus node

address in a RS-485 network wired on the

first RS-485 port

Networks /

UART1 (1)

Baud Rate

- - -

- - -

- - -

9600

Modbus communication baud rate in a

RS-485 network wired on the first RS-485

port

1200

= 1,200 baud

2400

= 2,400 baud

4800

= 4,800 baud

9600

= 9,600 baud

19200

= 19,200 baud

28800

= 28,000 baud

38400

= 38,400 baud

57600

= 57,600 baud

Networks /

UART1 (1)

Parity

- - -

- - -

- - -

EVEN

Modbus communication parity in a RS-485

network wired on the first RS-485 port

NONE

= no parity

ODD

= odd

EVEN

= even

Networks /

UART1 (1)

Stop

- - -

- - -

- - -

1 BIT

Modbus communication stop bit number in a

RS-485 network wired on the first RS-485

port

1 BIT

= 1 bit

2 BIT

= 2 bit

Networks /

UART2 (2)

Address

1

247

- - -

1

local (or of the controller) Modbus node

address in a RS-485 network wired on the

second RS-485 port

Advertising