Parameters (1)

AI3

- - -

- - -

- - -

NTC

kind of probe analog input 3

PTC

= PTC probe

NTC

= NTC probe

0-20mA = 0-20 mA transducer

4-20mA = 4-20 mA transducer

0-5V

= 0-5 V ratiometric transducer

0-10V

= 0-10 V ratiometric transducer

PT1000 = Pt 1000 probe

Parameters (1)

AI Err Time

0

240

s

2

analog inputs time-out (after this time without

communication with an analog input, the

controller signals the analog input error)

Parameters (1)

AO1

- - -

- - -

- - -

PWM

kind of signal analog input 1

PWM

= PWM (Pulse With Modulation)

Parameters (1)

AO2

- - -

- - -

- - -

0-10V

kind of signal analog input 2

0-20mA = 0-20 mA

4-20mA = 4-20 mA

0-10V

= 0-10 V

Parameters (1)

AO3

- - -

- - -

- - -

0-10V

kind of signal analog input 3

0-20mA = 0-20 mA

4-20mA = 4-20 mA

0-10V

= 0-10 V

Parameters (1)

CosPhi 10us

- - -

- - -

- - -

- - -

reserved

Parameters (2)

[ press button

RIGHT to

show it ]

I/O Timeout

1

240

s

60

time-out of the CANbus communication for

the test of the remote values of the I / O

(after

this

time

without

CANbus

communication, the I / O of the controller is

disabled)

Parameters (2)

[ press button

RIGHT to

show it ]

En. Prg Level

- - -

- - -

- - -

NO

enabling the access to the first level page

pressing a combination of buttons

YES

= yes, operating as follows:

-

keep pressed 3 s button

ENTER to gain access

to the first page of

level 1

-

keep

pressed

3

s

buttons

ENTER

and

ESC to gain access to

the first page of level 2

-

keep

pressed

3

s

buttons

LEFT

and

RIGHT to gain access to

the first page of level 3

Advertising