background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 50 of 116

ANALOG INPUTS

Analog inputs.

Each analog input is configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric /

0-10 V transducers.

Terminal

Meaning

AI1

analog input 1

AI2

analog input 2

AI3

analog input 3

GND

ground

+5V

power supply 0-5 V ratiometric transducers (5 VDC, 40 mA max.)

+24V

power supply 0-20 mA / 4-20 mA / 0-10 V transducers (24 VDC, 120 mA max.)

The maximum length of the connecting cables of the analog inputs and the one of the power supply of the transducers is

100 m (328 ft).

The expansion incorporates a restorable thermal protection of the power supplies against the short circuit and the overload.

For the settings about the analog inputs look at chapter 6 “CONFIGURATION”.

PROG

Port to update the firmware of the instrument.

POWER SUPPLY

Power supply.

Terminal

Meaning

V

power supply expansion (24 VAC / 20... 40 VDC)

V

power supply expansion (24 VAC / 20... 40 VDC)

The maximum length of the connecting cables of the power supply of the expansion is 30 m (98 ft).

Protect the power supply with a fuse rated 0.8A-T 250 V.

If the expansion is powered in direct current, one will not have to respect the polarity of the power supply voltage.

Advertising