The maximum length of the connecting cables of the CAN port depends on the baud rate of the CANbus communication, as

follows:

-

1,000 m (3,280 ft) with baud rate 20,000 baud

-

500 m (1,640 ft) with baud rate 50,000 baud

-

250 m (820 ft) with baud rate 125,000 baud

-

50 m (164 ft) with baud rate 500,000 baud.

Connect the CAN port using a twisted pair.

For the settings about the CAN port look at chapter 6 “CONFIGURATION”.

DIGITAL OUTPUTS

In c-pro 3 EXP hecto.

Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).

Terminal

Meaning

CO1/2

common digital outputs 1 and 2

NO1

normally open contact digital output 1

NO2

normally open contact digital output 2

CO3

common digital output 3

NO3

normally open contact digital output 3

CO4/5

common digital outputs 4 and 5

NO4

normally open contact digital output 4

NO5

normally open contact digital output 5

Digital output 6 (electromechanical relay).

Terminal

Meaning

CO6

common digital output 6

NO6

normally open contact digital output 6

NC6

normally closed contact digital output 6

The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).

The maximum current allowed on the loads is 10 A.