Networks / CAN

Bus

[ press button

RIGHT to

show it ]

BTR(1)

1

15

- - -

15

reserved

Networks / BMS

(4)

MAC ID

-1

127

- - -

-1

local (or of the controller) BACnet MS/TP

node address

-1

= not enabled

Networks / BMS

(4)

Baud Rate

- - -

- - -

- - -

19200

BACnet MS/TP communication baud rate

9600

= 9,600 baud

19200

= 19,200 baud

38400

= 28,000 baud

76800

= 76,800 baud

Networks / BMS

(4)

Max Master

0

127

- - -

127

maximum number of master in a BACnet

MS/TP network

Networks / BMS

(4)

Max InfoFram

1

127

- - -

3

maximum number of packages transmitted

as master before giving the token

Networks / BMS

(4)

Device ID

1

4194303

- - -

108

identity in a BACnet MS/TP multinetwork

Networks /

UART1 (1)

Address

1

247

- - -

1

local (or of the controller) Modbus node

address in a RS-485 network wired on the

first RS-485 port

Networks /

UART1 (1)

Baud Rate

- - -

- - -

- - -

9600

Modbus communication baud rate in a

RS-485 network wired on the first RS-485

port

1200

= 1,200 baud

2400

= 2,400 baud

4800

= 4,800 baud

9600

= 9,600 baud

19200

= 19,200 baud

28800

= 28,000 baud

38400

= 38,400 baud

57600

= 57,600 baud

Networks /

UART1 (1)

Parity

- - -

- - -

- - -

EVEN

Modbus communication parity in a RS-485

network wired on the first RS-485 port

NONE

= no parity

ODD

= odd

EVEN

= even