c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 36 of 116

3

not connected

4

D0 = B = - (terminal 0 of the transceiver)

5

D1 = A = + (terminale 1 of the transceiver)

6

not connected

7

not connected

8

not connected

The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications

and implementation guides manual (the document is available on the internet site www.modbus.org).

Connect the RS-485 port using a twisted pair.

The following table shows the function codes supported by the controller.

Function

code

Meaning

FC 01

read coils

FC 02

read discrete inputs

FC 03

read multiple registers

FC 04

read input registers

FC 05

write single coil

FC 06

write single register

FC 08

diagnostic

FC 15

write multiple coils

FC 16

write multiple registers

FC 23

read write multiple registers

For the settings about the RS-485 port look at chapter 6 “CONFIGURATION”.