EVCO EPH4EXP Hardware manual User Manual

Page 75

Advertising
background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 75 of 116

Password

Timeout

0

240

s

240

time-out of the passwords to gain access to

the levels (after this time since the last

operation with the buttons, to gain access to

the level one has to set a password again, if

foreseen)

Diagnostic

FRAM

parameter available in read only modality

time-out of the passwords to gain access to

the levels (after this time since the last

operation with the buttons, to gain access to

the level one has to set a password again, if

foreseen)

Diagnostic

RTC

parameter available in read only modality

non volatile memory status

ok

= not in error

err

= in error

Diagnostic

STACK

parameter available in read only modality

clock status

ok

= not in error

err

= in error

low

= loss of data

Diagnostic

Power Supply

parameter available in read only modality

stack status

ok

= not in error

err

= in error (because of overflow)

Diagnostic

5V Ratio

parameter available in read only modality

power supply voltage status

ok

= not in error

err

= in error (because of out of

range voltage)

Diagnostic

24V Sensor

parameter available in read only modality

status of the power supply voltage of the

ratiometric transducers

ok

= not in error

err

= in error (because of out of

range voltage)

Diagnostic

24V CAN bus

parameter available in read only modality

status of the power supply voltage of the

user interface

ok

= not in error

err

= in error (because of out of

range voltage)

Diagnostic

Math

parameter available in read only modality

Math status

ok

= not in error

err

= in error (because of overflow,

underflow, division by zero or

NaN)

Advertising
This manual is related to the following products: