EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 111 of 116

PWM analog outputs (but the analog outputs 4 and 5 of c-pro 3 mega+)

Driving power supply:

24 VDC (+16% -25%), 50 mA max.

Frequency:

the same as the one of the phase powering the device.

Protection:

no protection.

0-20 mA / 4-20 mA analog outputs

Input resistance:

40... 300

.

Accuracy:

±3% of the full scale.

Resolution:

0.05 mA.

Conversion time:

1 s.

Protection:

restorable thermal protection against the short circuit and the

overload.

0-10 V analog outputs

Input resistance:

1K

min.

Accuracy:

+2% -5% of the full scale for users having impedance between

1 and 5K

, ±2% of the full scale for users having impedance

> of 5K

.

Resolution:

0.01 V.

Conversion time:

1 s.

Protection:

restorable thermal protection against the short circuit and the

overload.

Digital outputs:

c-pro 3 hecto

c-pro 3 mega and c-pro 3

NODE mega

c-pro 3 EXP hecto

6 outputs (electromechanical

relays):

five 5 res. A @

250 VAC (6,000

cycles)

SPST

outputs (K1, K2,

K3, K4 and K5)

one 8 res. A @

250 VAC (6,000

cycles)

SPDT

output (K6).

8 outputs (electromechanical

relays):

three 5 res. A @

250 VAC (6,000

cycles)

SPST

outputs (K1, K5

and K7)

four 8 res. A @

250 VAC (6,000

cycles)

SPST

outputs (K2, K3,

K4 and K6)

one 8 res. A @

250 VAC (6,000

cycles)

SPDT

output (K8).

6 outputs (electromechanical

relays):

five 5 res. A @

250 VAC (6,000

cycles)

SPST

outputs (K1, K2,

K3, K4 and K5)

one 8 res. A @

250 VAC (6,000

cycles)

SPDT

output (K6).

c-pro 3 hecto+

c-pro 3 mega+

c-pro 3 EXP hecto+

Advertising